• XCNet-MB-S Ethernet Module for ModbusASCII/RTU Device Data Acquisition Support AP/STA/AP+STA Mode
  • XCNet-MB-S Ethernet Module for ModbusASCII/RTU Device Data Acquisition Support AP/STA/AP+STA Mode

XCNet-MB-S Ethernet Module for ModbusASCII/RTU Device Data Acquisition Support AP/STA/AP+STA Mode

Availability: In stock, usually dispatched in 1 business day

  • Price:$242.91
  • Price in reward points: 2429 Reward Points: 24
  • Quantity 3+ units 10+ units 30+ units 50+ units More
    Price /Unit $238.05 $233.19 $225.91 $216.19 Contact US
Quantity:

XCNet-MB-S Ethernet Module for ModbusASCII/RTU Device Data Acquisition Support AP/STA/AP+STA Mode

Description:

- BCNet-MB-S is used for Ethernet data acquisition of ModbusASCII/RTU devices (instruments, frequency converters, PLCs, etc.). The module integrates WiFi functions, supports AP mode, STA mode, and AP+STA mode, with rubber bars and magnetic antennas, making it easy to build a WiFi network. ModbusASCII/RTU device programming and data acquisition can be directly carried out through WiFi.
- BCNet-MB-S adopts a plug and play design that does not occupy the communication port of ModbusASCII/RTU devices. That is, the programming software/upper computer software monitors device data through Ethernet, and the ModbusASCII/RTU master station can communicate with ModbusASCII/RTU devices through a multiplexing interface. It supports the vast majority of SCADA software in the field of industrial control and supports Modbus TCP and Modbus UDP communication methods.

Features:
- Installed on a 35mm rail without the need for external power supply. The COM1 port is connected to the RS485 interface of the device, and the COM2 expansion port is used for Modbus master station communication.
- Parameter settings and running diagnostics can be performed on devices through a WEB server or the configuration diagnostic tool BCDevice.
- Suitable for network upgrade of ModbusASCII/RTU, device data can be directly read through upper computer configuration software that supports ModbusTCP.
- Integrated WiFi functions, supporting AP mode, STA mode, and AP+STA mode.
- RS485/RS232 device data acquisition can be achieved through WiFi or Ethernet.
- Supports asynchronous and uninterrupted ModbusTCP access mode, which is different from the traditional master-slave reply half duplex mode and provides more efficient data access. The ModbusTCP request from the client can send multiple ModbusTCP requests simultaneously without waiting for a response from the device, and the module will automatically asynchronously reply to the response frame.
- Supports ModbusTCP, ModbusUDP, ModbusRTU, and ModbusASCII communication protocols, supports various configuration software and OPC, and accesses device data through the Modbus protocol.
- ModbusTCP/UDP can be used to realize High-level language programming (such as VB, VC, C #, etc.), realize data communication with PLC, and facilitate the development of production management system.
- Supports 32 Modbus TCP client connections.
- Support firmware updates on the user side through Ethernet.

Specification:
- Status display: Pwr, Com1, Com2, WiFi
- Ethernet interface: IE Link/Active indicator, automatic polarity crossing
- Interface type: RJ45 Female socket
- Transmission speed rate: 10/100Mbps
- Supported protocol: Modbus TCP/Modbus UDP
- TCP connection: 32 maximum

WiFi:

- Interface: 802.11 b/g/n 2.4G - 2.5G
- Interface type: External high gain antenna
- Transmission power: +26dBm (MAX, 2.4G 802.11b/g/n)
- Receiving sensitivity: -89dBm (802.11b)/-74dBm (802.11g), -72dBm (802.11n)
- Wireless type: Station/AP mode
- Protection mechanism: WPA-PSK/WPA2-PSK/WEP
- Supported protocol: Modbus TCP/Modbus UDP
- TCP connection: 32 maximum

X1: (for PLC):
- Interface type: RJ485
- Transmission speed rate: 9.6K, 19.2K, 38.4K, 57.6K, 115.2K
- Supported protocol: Modbus RTU/Modbus ASCII

X2 (for HDMI):
- Interface type: RJ485
- Transmission speed rate: 9.6K, 19.2K, 38.4K, 57.6K, 115.2K
- Supported protocol: Modbus RTU/Modbus ASCII

General:
- Configuration software: for WINCC/for MCGS/for King View/for Power Control/for Fame View/for IFIX/for INTOUCH
- OPC software: for KepWare OPC
- Diagnostic and parameter setting: IE browser, 192.168.1.188 by default, BCDevice search configuration tool
- Power supply: 24V DC
- Voltage type: 24V DC/100mA
- Working temperature: 0 ~ 60℃
- Working humidity: 95% non-condensing
- EMC: 2014/30/EU
- Size (L x W x H): 115 x 27 x 75mm
- Weight: 150g

Package Included:
- 1 x Ethernet Module

Write a review

Note: We will keep it confidential.
Note: HTML is not translated!
 
Captcha